operate automatically from Saturday turn_off time to Monday turn_on time. If the AUTO mode is disabled
by the weekly operation schedule, then the AUTO led will flash, otherwise it is steadily on.
Pgm Definition Unit Std Description
51 Monday turn_on - 24.0
52 Monday turn_off - 24.0
53 Tuesday turn_on - 24.0
54 Tuesday turn_off - 24.0
55 Wednesday turn_on - 24.0
56 Wednesday turn_off - 24.0
57 Thursday turn_on - 24.0
58 Thursday turn_off - 24.0
59 Friday turn_on - 24.0
60 Friday turn_off - 24.0
61 Saturday turn_on - 24.0
62 Saturday turn_off - 24.0
63 Sunday turn_on - 24.0
64 Sunday turn_off - 24.0
The parameters from P_065 to P_082 define the functions of relay outputs. The unit has 6 relay
outputs and 2 of them have programmable functions. The fixed function relays are Fuel, Start, Mains
Contactor and Generator Contactor.
The relays may be extended up to 22 using Relay Extension Modules. RELAY-1 and RELAY-2
with programmable functions are inside the unit. Other relays are in the optional Extension Modules.
The function of a programmable relay output may be selected from the below list.
RELAY FUNCTON LIST
Pgm Description Std
65 RELAY-1 function 01
66 RELAY-2 function 03
67 RELAY-3 function 16
68 RELAY-4 function 17
69 RELAY-5 function 18
70 RELAY-6 function 19
71 RELAY-7 function 20
72 RELAY-8 function 21
73 RELAY-9 function 22
74 RELAY-10 function 23
75 RELAY-11 function 24
76 RELAY-12 function 25
77 RELAY-13 function 26
78 RELAY-14 function 27
79 RELAY-15 function 28
80 RELAY-16 function 29
81 RELAY-17 function 30
82 RELAY-18 function 31
00 Fuel
01 Horn
02 Start
03 Stop
04 Gen. Contactor
05 mains Contactor
06 Choke
07 Preheat
08 Alarm
09 Warning
10 Alarm+Warning
11 Automatic ready
12 Week. on time
13 Exerciser on
14 -
15 -
16 Oil switch alarm
17 Temp switch alarm
18 Level switch alarm
19 Rectifier alarm
20 Emerg.Stop alarm
21 Spare-1 Alarm
22 Spare-2 Alarm
23 -
24 Oil sender alarm
25 Temp sender alarm
26 Speed alarm
27 Start fail alarm
28 Charge alarm
29 Overload alarm
30 Voltage alarm
31 Battery High alarm
32 Oil switch warning
33 Temp switch warn.
34 Level switch warn.
35 Rectifier warning
36 Emerg Stop warn.
37 Spare-1 warning
38 Spare-2 warning
39 -
40 Oil sender warning
41 Temp sender warn.
42 Speed warning
43 Stop Fail warning
44 Charge warning
45 Battery low warning
46 -
47 Battery high warn.
Vista de pagina 19