Datakom DKG-307 Manual de usuario Pagina 46

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 54
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 45
DKG-307 User Manual V-42 (24.05.2013)
- 46 -
Spare1 Input Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_214
Action
2
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_215
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_216
Latching
0
0: Non latching
1: Latching
P_217
Contact type
0
0: Normally open
1: Normally closed
P_218
Switching
0
0: Battery negative
1: Battery positive
P_219
Response delay
0
0: No delay
1: Delayed (4sec)
Spare-2 Input Input Configuration
PGM
Parameter Definition
Unit
Fac.Set
Description
P_220
Action
2
0: Shutdown (the engine stops immediately)
1: Load Dump (the engine stops after cooldown)
2: Warning (the horn relay operates)
3: No operation
P_221
Sampling
0
0: Always
1: After holdoff timer
2: When mains present
P_222
Latching
0
0: Non latching
1: Latching
P_223
Contact type
0
0: Normally open
1: Normally closed
P_224
Switching
0
0: Battery negative
1: Battery positive
P_225
Response delay
0
0: No delay
1: Delayed (4sec)
Vista de pagina 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 52 53 54

Comentarios a estos manuales

Sin comentarios