Datakom DKG-307 Manual de usuario Pagina 30

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 54
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 29
DKG-307 User Manual V-42 (24.05.2013)
- 30 -
The unit keeps record of the last 100 events in order to supply information for the service personal.
The genset status information and a comprehensive set of measured values are stored within the
event memory. The events are recorded with a time stamp which comes from the internal real time
clock circuit of the unit.
The events are stored in a circular memory. This means that a new coming event will erase the oldest
recorded event.
Events are kept in a non-volatile memory and are not affected from power failures.
Events are not visible on the device display. They can be downloaded to the computer and saved in
an Excel file.
Event sources are:
-Shutdown alarms, Load dump alarms, Warnings
-Engine crank starts
-Periodic records.
Event record contents are:
Event type (alarms, mode change, periodic, etc…)
Date and time
Genset operating mode (AUTO, MANUAL,OFF,TEST, LOAD TEST)
Genset operation status (mains ok, running, cooldown etc…)
Genset phase voltages L1-L2-L3
Genset phase currents L1-L2-L3
Genset frequency
Genset active power (KW)
Genset power factor
Engine rpm
Oil pressure
Coolant temperature
Fuel level
Battery voltage
Mains phase voltages L1-L2-L3
Mains frequency
Digital input statuses
Charge input status
J1939 VAlues (if applicable)
The unit provides a set of non resettable incremental counters for statistical purposes.
The counters consist on:
-total engine hours
-total genset KWh
-engine hours to service
-time to service
-total engine cranks
-total genset runs
These counters are kept in a non-volatile memory and are not affected from power failures.
11. STATISTICAL COUNTERS
10. EVENT LOGGING
Vista de pagina 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 53 54