DKG-307 User Manual V-42 (24.05.2013)
- 37 -
Reverse power
warning limit
If the genset power is negative and goes above
this limit then a REVERSE POWER warning will
be generated.
Reverse power
loaddumpg limit
If the genset power is negative and goes above
this limit then a REVERSE POWER loaddump will
be generated.
If the genset power goes below this limit then the
load shedding relay will be deactivated.
If the genset power goes above this limit then the
load shedding relay will be activated.
If the fuel level measured from the sender input
falls below this level, then the FUEL PUMP
function will become active.
If the fuel level measured from the sender input
goes above this level, then the FUEL PUMP
function will become passive.
If the coolant temp is above this limit then the fan
relay function will become active.
If the coolant temp is below this limit then the fan
relay function will become inactive.
This parameter defines the engine heating
method. The genset will not take the load before
engine heating is completed.
0: engine is heated during Engine Heating Timer.
1: engine is heated until the coolant temperature
reaches the Engine Heating Temperature and at
least during the Engine Heating Timer.
When the genset frequency reaches this limit, the
engine is supposed running and the crank output
will release.
Crank Stop with Oil
Pressure
0: no crank stop with oil pressure
1: cranking is stopped when oil presure switch is
open or the oil pressure measured is above
shutdown limit.
0: no crank stop with charge input
1: cranking is stopped when the charge alternator
voltage is established.
Charge Alternator
Shutdown
0: The charge input generates CHARGE FAIL
warning, and does not stop the engine.
1: The charge input generates CHARGE FAIL
alarm, and stops the engine.
0: Display Line to Neutral voltages as default
1: Display Line to Line voltages as default
0: oil pressure display in bars
1: oil pressure display in psi
0: temperature display in degrees C
1: temperature display in degrees F
Following parameters are in “high” priority group.