Datakom DKG-307 Manual de usuario Pagina 37

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 54
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 36
DKG-307 User Manual V-42 (24.05.2013)
- 37 -
PGM
Parameter Definition
Unit
Fact.Set
Description
P_059
Reverse power
warning limit
KW
0
If the genset power is negative and goes above
this limit then a REVERSE POWER warning will
be generated.
P_060
Reverse power
loaddumpg limit
KW
0
If the genset power is negative and goes above
this limit then a REVERSE POWER loaddump will
be generated.
P_061
Load Shedding Low
Limit
KW
0
If the genset power goes below this limit then the
load shedding relay will be deactivated.
P_062
Load Shedding High
Limit
KW
0
If the genset power goes above this limit then the
load shedding relay will be activated.
P_063
Fuel Pump Low Limit
%
20
If the fuel level measured from the sender input
falls below this level, then the FUEL PUMP
function will become active.
P_064
Fuel Pump High Limit
%
80
If the fuel level measured from the sender input
goes above this level, then the FUEL PUMP
function will become passive.
P_065
Fan turn-on temp
°C
90
If the coolant temp is above this limit then the fan
relay function will become active.
P_066
Fan turn-off temp
°C
80
If the coolant temp is below this limit then the fan
relay function will become inactive.
P_067
Engine Heating
Method
-
0
This parameter defines the engine heating
method. The genset will not take the load before
engine heating is completed.
0: engine is heated during Engine Heating Timer.
1: engine is heated until the coolant temperature
reaches the Engine Heating Temperature and at
least during the Engine Heating Timer.
P_068
Crank Cut Frequency
Hz
10.0
When the genset frequency reaches this limit, the
engine is supposed running and the crank output
will release.
P_069
Crank Stop with Oil
Pressure
-
0
0: no crank stop with oil pressure
1: cranking is stopped when oil presure switch is
open or the oil pressure measured is above
shutdown limit.
P_070
Crank Stop with
Charge
-
0
0: no crank stop with charge input
1: cranking is stopped when the charge alternator
voltage is established.
P_071
Charge Alternator
Shutdown
-
0
0: The charge input generates CHARGE FAIL
warning, and does not stop the engine.
1: The charge input generates CHARGE FAIL
alarm, and stops the engine.
P_072
Line-to-Line Voltages
-
0
0: Display Line to Neutral voltages as default
1: Display Line to Line voltages as default
P_073
Oil Pressure in psi
-
0
0: oil pressure display in bars
1: oil pressure display in psi
P_074
Temperature in °F
-
0
0: temperature display in degrees C
1: temperature display in degrees F
Following parameters are in “high” priority group.
Vista de pagina 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 53 54

Comentarios a estos manuales

Sin comentarios